2×4/0+4/0awg Lepas Aluminum Conductor Triplex Overhead Service Drop Cable Wire
Triplex Service Drop Cable 4/0AWG Lepas #4/0
Code Word: Lepas
Size AWG (Phase Conductors): 4/0
Voltage: 600V
Number of cores: Triplex
Package : Export wooden drum & iron wooden drum or as customer require
4/0-4/0-4/0 Lepas Aluminum Conductor Triplex Overhead Service Drop Cable Wire Application
4/0 Lepas Aluminum Conductor Overhead Service Drop Cable Wirehas three conductors, with one of them being for neutral path, and two electrodes. Used to supply power, usually from a pole-mounted transformer, to the user’s service head where connection to the service entrance cable is made. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for cross-linked polyethylene (XLPE) insulated conductors.
4/0-4/0-4/0 Lepas Aluminum Conductor Triplex Overhead Service Drop Cable Wire Standard
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.• B-231 Aluminum Conductors, Concentric-Lay-Stranded.
• B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
• B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
• ICEA S-76-474-Neutral-supported Power Cable Assemblies With Weather-Resistant Extruded Insulation Rated 600Volts.
CONSTRUCTION :
4/0-4/0-4/0 Lepas Aluminum Conductor Triplex Overhead Service Drop Cable Wire Construction
Phase Conductor | Strand or Compressed 1350-H19 Series Aluminum Conductor. |
Neutral(Messenger)Conductor | Bare AAAC messenger. |
Insulation | Black Cross Linked Polyethylene (XLP) Insulation. |
TECHNICAL DATA :
4/0-4/0-4/0 Lepas Aluminum Conductor Triplex Overhead Service Drop Cable Wire Technical Data
Rated voltage | V | 600 |
Test voltage | Veff kV/Hz | 4/50 |
Laying temperature | °C | min. -5 |
Operating temperature | °C | -30 ~ +90 |
Conductor temperature | °C | max. +90 |
Short-circuit temperature | °C/s | max. +250 /5 |
Bending radius (min.) | mm | 20 × Ø of cable |
Technical Parameter
| Code Name | Lepas |
| Phase Conductor Material | AAC |
| Phase Conductor Size (awg) | 4/0 |
| Phase Conductor Stranding | 19 |
| Phase Conductor insulation Material | XLPE |
| Phase Conductor Insulation Thickness (mils) | 60 |
| Bare Neutral Messenger Material | AAAC |
| Bare Neutral Messenger Size(awg) | 4/0 |
| Bare Neutral Messenger Stranding | 7 |
| Bare Neutral Messenger Breaking Strength (Lbs) | 8560 |
| Weight Per (Lbs/1000 ft) | 725 |
| Ampacity (Amps) | 315 |
YOU MAY LIKE
Related products
-
Triplex Overhead Service Drop Cable
2×1/0+1/0awg Cenia Aluminum Conductor Triplex Overhead Service Drop Cable Wire
-
Triplex Overhead Service Drop Cable
2×2+2awg Conch Aluminum Conductor Triplex Overhead Service Drop Cable Wire
-
Triplex Overhead Service Drop Cable
2×2+2awg Shrimp Aluminum Conductor Triplex Overhead Service Drop Cable Wire
-
Triplex Overhead Service Drop Cable
2×4+4awg Oyster Aluminum Conductor Triplex Overhead Service Drop Cable Wire
-
Triplex Overhead Service Drop Cable
2×4+4awg Prawn Aluminum Conductor Triplex Overhead Service Drop Cable Wire
-
Triplex Overhead Service Drop Cable
2×6+6awg Patella Aluminum Conductor Triplex Overhead Service Drop Cable Wire
-
Triplex Overhead Service Drop Cable
2×6+6awg Hippa Aluminum Conductor Triplex Overhead Service Drop Cable Wire
-
Triplex Overhead Service Drop Cable
NS75/NS90 Triplex Unjacketed Overhead Neutral Supported Cable

