2×3/0+3/0awg Cherrystone Aluminum Conductor Triplex Overhead Service Drop Cable Wire

Triplex Service Drop Cable 3/0AWG Cherrystone #3/0

Code Word: Cherrystone

Size AWG (Phase Conductors): 3/0

Voltage: 600V

Number of cores: Triplex

Package : Export wooden drum & iron wooden drum or as customer require

3/0-3/0-3/0 Cherrystone Aluminum Conductor Triplex Overhead Service Drop Cable Wire Application

3/0-3/0-3/0 Cherrystone Aluminum Conductor Triplex Overhead Service Drop Cable Wire has three conductors, with one of them being for neutral path, and two electrodes. The aluminum triplex cable is an electrical cable used to supply power, usually from a pole-mounted transformer, to the user’s service head where connection to the service entrance cable is made. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for cross-linked polyethylene (XLPE) insulated conductors.


3/0-3/0-3/0 Cherrystone Aluminum Conductor Triplex Overhead Service Drop Cable Wire Standard
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum Conductors, Concentric-Lay-Stranded.
• B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
• B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
• ICEA S-76-474-Neutral-supported Power Cable Assemblies With Weather-Resistant Extruded Insulation Rated 600Volts 
CONSTRUCTION :
3/0-3/0-3/0 Cherrystone Aluminum Conductor Triplex Overhead Service Drop Cable Wire Construction

Phase Conductor

Strand or Compressed 1350-H19 Series Aluminum Conductor.

Neutral(Messenger)Conductor

Bare ACSR messenger. 

Insulation

Black Cross Linked Polyethylene (XLP) Insulation.

 
TECHNICAL DATA :
3/0-3/0-3/0 Cherrystone Aluminum Conductor Triplex Overhead Service Drop Cable Wire Technical Data

Rated voltage

V

600

Test voltage

Veff kV/Hz

4/50

Laying temperature

°C

min. -5

Operating temperature

°C

-30 ~ +90

Conductor temperature

°C

max. +90

Short-circuit temperature

°C/s

max. +250 /5

Bending radius (min.)

mm

20 × Ø of cable

 

Technical Parameter

Code WordPhase ConductorsBare Neutral MessengerWeight (lbs) per 1000 ft.Ampacity (Amps)
Size AWGStrandInsulation Thickness (mils)Size AWG*StrandBreaking Strength (lbs)XLPPolyXLPPoly
Paludina6Solid4566/11,1901141138570
Voluta67/w4566/11,1901151128570
Whelk4Solid4546/11,86016316111090
Periwinkle47/w4546/11,86017216911090
Conch27/w4526/12,850262257150115
Neritina1/07/w601/06/14,380420414200155
Cenia1/019/w601/06/114,380414408200155
Runcina2/07/w602/06/15,310519512230180
Triton2/019/w602/06/15,310511505230180
Cherrystone3/07/w603/06/16,620656643260205
Mursia3/019/w603/06/16,620633626260205
Razor4/07/w604/06/18,350814799300235
Zuzara4/019/w604/06/18,350785777300235
Limpet33619/w8033618/18,68011611147380290
Scroll to Top