2×4+4awg Whelk Triplex Aluminum Conductor Triplex Overhead Service Drop Cable Wire

Triplex Service Drop Cable 4AWG Whelk #4

Code Word: Whelk

Size AWG (Phase Conductors): 4

Voltage: 600V

Number of cores: Triplex

Package : Export wooden drum & iron wooden drum or as customer require

4-4-4 Whelk Aluminum Conductor Triplex Overhead Service Drop Cable Wire Application
4-4-4 Whelk Triplex aluminum wire has three conductors, with one of them being for neutral path, and two electrodes. Primarily used for 120 volt overhead service applications such as street lighting, outdoor lighting, and temporary service for construction. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for crosslinked polyethylene (XLP) insulated conductors.A bare messenger wire of this electrical cable is bonded closely on the two insulated aluminum conductors, which are individually insulated with black cross-linked polyethylene for protection.
4-4-4 Whelk Triplex Aluminum Conductor Triplex Overhead Service Drop Cable Wire Standard


• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum Conductors, Concentric-Lay-Stranded.
• B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
• B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
• ICEA S-76-474-Neutral-supported Power Cable Assemblies With Weather-Resistant Extruded Insulation Rated 600Volts

 

CONSTRUCTION :
4-4-4 Whelk Aluminum Conductor Triplex Overhead Service Drop Cable Wire Construction

Phase Conductor

Strand or Compressed 1350-H19 Series Aluminum Conductor.

Neutral(Messenger )Conductor

Bare ACSR messenger. 

Insulation

Black Cross Linked Polyethylene (XLP) Insulation.



 
TECHNICAL DATA :
4-4-4 Whelk Aluminum Conductor Triplex Overhead Service Drop Cable Wire Technical Data

Rated voltage

V

600

Test voltage

Veff kV/Hz

4/50

Laying temperature

°C

min. -5

Operating temperature

°C

-30 ~ +90

Conductor temperature

°C

max. +90

Short-circuit temperature

°C/s

max. +250 /5

Bending radius (min.)

mm

20 × Ø of cable

Technical Parameter

Code NameWhelk
Phase Conductor MaterialAAC
Phase Conductor Size (awg)4
Phase Conductor Stranding1
Phase Conductor insulation MaterialXLPE
Phase Conductor Insulation Thickness (mils)45
Bare Neutral Messenger MaterialACSR
Bare Neutral Messenger Size(awg)4
Bare Neutral Messenger Stranding6/1
Bare Neutral Messenger Breaking Strength (Lbs)1860 
Weight Per (Lbs/1000 ft) 176
Ampacity (Amps)115 
Scroll to Top

Leave a message