Copper Conductor Triplex Service Drop Cable 600V

Copper Conductor Triplex Service Drop Cable 600V

Conductor: Stranded compressed soft copper

Insulation: Thermoplastic Polyethylene or Cross-linked Polyethylene

Voltage: 600V

Number of cores: Triplex

Package: Export wooden drum & iron wooden drum or as customer require

Copper Triplex Service Drop Cable Application

Used to supply power, usually from a pole-mounted transformer, to the user’s service head where connection to the service entrance cable is made. Also suitable for installations for street lighting, security lights, and temporary service for construction. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 75 ºC for polyethylene insulated conductors and 90 ºC for cross-linked polyethylene (XLP) insulated conductors.Copper Triplex Service Drop Cable SpecificationsMeets or exceeds the following ASTM specifications:
B-1 Hard-Drawn Copper Wire.
B-3 Soft or Annealed Copper Wire.
B-8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft.
Meets or exceeds all applicable requirements of ANSI/ICEA S-76-474 for polyethylene and cross-linked polyethylene insulated conductors. 

 
CONSTRUCTION :
Copper Triplex Overhead Service Drop Cable Wire Construction

Conductors are concentrically stranded compressed soft copper insulated with either cross-linked polyethylene, or conventional polyethylene.
Neutral messengers are either solid or concentrically stranded bare hard-drawn copper.

Notes:
Code words for XLP insulated products are formed by adding “”XLP”” to the conventional polyethylene code words above (e.g.-Theta/XLP).
Ampacity figures for black insulation only. Based on conductor temperature of 75 ºC for polyethylene insulated conductors, 90 ºC for XLP insulated conductors, ambient temperature of 40 ºC 2 ft./sec. wind in sun. 

 
TECHNICAL DATA :
Copper Triplex Overhead Service Drop Cable Wire Technical Data

Rated voltage

kV

0.6/1

Test voltage

Veff kV/Hz

4/50

Laying temperature

°C

min. -5

Operating temperature

°C

-30 ~ +90

Conductor temperature

°C

max. +90

Short-circuit temperature

°C/s

max. +250 /5

Bending radius (min.)

mm

20 × Ø of cable

Technical Parameter

Code WordCopper Phase ConductorBare Copper Neutral MessengerWeight Per 1000 Ft. (lbs.)Allowable Ampacities+
Size (AWG)StrandingInsulation Thickness (mils.)Size (AWG)StrandingRated Strength (lbs.)PolyethyleneXLPPolyethyleneXLP
Pica874510SOLID5291641687085
Biodoni87458SOLID8261851897085
Garamond8745877771861907085
Tudor67458SOLID82625426090110
Futura67456SOLID128028128890110
Gothic674567122828529190110
Nonpareil47456SOLID1280390396115145
Ionic47454SOLID1970438443115145
Caslon4745471938442447115145
Minion27454SOLID1970609617155195
Primer2745471938614622155195
Century2745273050692701155195
Corinthian1/019601/07475210551066205265
Doric2/019602/07592613191331235300
Tuscan3/019603/07736616651667275350
Composite4/019604/07915420882085315405