N2XSBY (YJV62) 3.6-6(7.2)kV (CU/XLPE/CTS/ATA/PVC)

Medium voltage cables for distribution networks, they are suitable for laying indoor, tunnel, cables trench and underground, it is able to bear external mechanical forces, but unable to bear heavy pulling force, it widely used in transformer stations, electric power plants and industrial plants.

Application

Gongniu Cable’s N2XSBY (CU/XLPE/STA/PVC) Power Cables are designed for use in power distribution networks. These versatile cables are suitable for various installation environments. You can install them indoors, within tunnels, in cable trenches, or lay them directly underground. They are widely used in transformer stations, electric power plants, and different industrial plants. While the N2XSBY cable can withstand external mechanical forces, it is not designed to bear heavy pulling tension.

Description

The N2XSBY cable from Gongniu Cable is built with quality components for reliable and safe operation.

  • Conductor: The cable features a Class 2 circular compacted copper conductor.
  • Conductor Screen: A non-metallic, semi-conducting compound is used for the conductor screen.
  • Insulation: We use Cross-Linked Polyethylene (XLPE) for its excellent insulating properties.
  • Insulation Screen: A non-metallic, semi-conducting compound also serves as the insulation screen.
  • Metallic Screen: A copper tape acts as the metallic screen.
  • Inner Sheath: The inner sheath is made of Polyvinyl Chloride (PVC).
  • Armour: For added protection, the cable is armored with non-magnetic steel tape.
  • Outer Sheath: A robust Polyvinyl Chloride (PVC) outer sheath encases the cable.

This Gongniu Cable product offers good electrical and mechanical properties. Key characteristics include minimal dielectric loss and high insulation resistance. Furthermore, the PVC outer sheath provides adequate resistance to grease, oil, and abrasion, ensuring durability in various conditions.

Specification

Our N2XSBY cables are manufactured in compliance with recognized international standards.

  • The conductors meet the requirements of IEC 60228 (Conductors of Insulated Cables).
  • The overall cable construction adheres to IEC 60502-2 (Power Cables with Extruded Insulation and Their Accessories for Rated Voltages from 1kV(Um=1.2kV) up to 30kV(Um=36kV) – Part 2: Cables for Rated Voltages of 6kV(Um=7.2kV) and 30kV(Um=36kV)).

 

 

 

N2XSBY/NA2XSBY (YJV62/YJLV62) 3.6-6(7.2)kV IEC 60502-2

No. of Cores
and Nominal
Cross Section
(mm²)
Nominal
Insulation
Thickness
(mm)
Nominal
Steel Tape
Thickness
(mm)
Nominal
Sheath
Thickness
(mm)
Approx.
Overall
Diameter
(mm)
Approx. Weight
(kg/km)
Max. DC Resistance
of Conductor at
20℃ (Ω/km)
Cu Al Cu Al
1X25 2.5 0.20 1.6 20.2 728 576 0.727 1.20
1X35 2.5 0.20 1.6 21.2 849 638 0.524 0.868
1X50 2.5 0.20 1.7 22.5 1006 720 0.387 0.641
1X70 2.5 0.20 1.7 24.2 1252 837 0.288 0.443
1X95 2.5 0.20 1.8 26.2 1559 985 0.193 0.320
1X120 2.5 0.20 1.8 27.4 1819 1093 0.153 0.253
1X150 2.5 0.20 1.9 29.1 2130 1233 0.124 0.206
1X185 2.5 0.20 1.9 30.8 2524 1394 0.0991 0.164
1X240 2.6 0.20 2.0 33.5 3130 1663 0.0754 0.125
1X300 2.8 0.50 2.2 37.7 4161 2322 0.0601 0.100
1X400 3.0 0.50 2.3 41.0 5109 2740 0.0470 0.0778
1X500 3.2 0.50 2.4 45.2 6290 3283 0.0366 0.0605
1X630 3.2 0.50 2.5 49.3 7813 3909 0.0283 0.0469