N2XY – YJV (Cu/XLPE/PVC)

These power cables are used for electricity supply in low voltage installation systems. They are well adapted to underground use in industrial applications with an additional mechanical protection. These cables can be fixed on cable trays, within conduits or fixed to walls.

Application

This power cable is designed for electricity supply in low voltage installation systems. It works well for underground use in industrial applications, especially when you add extra mechanical protection. You can install this versatile cable on cable trays, inside conduits, or fix it directly to walls.

Description

The N2XY – YJV power cable from Gongniu Cable features a high-quality copper conductor. You can choose between Class 1 solid or Class 2 stranded copper, available in circular or circular compacted forms, to best suit your project needs.

The core of its performance lies in its Cross-linked Polyethylene (XLPE) insulation. This XLPE insulation provides excellent electrical and mechanical properties. It allows the cable to handle greater power capacity, ensures minimum dielectric losses, and offers high insulation resistance. This means more efficient power delivery for your applications.

For protection, the cable is encased in a durable Polyvinyl Chloride (PVC) outer sheath. This PVC sheath gives the cable good resistance to oil and abrasion, making it suitable for demanding environments. Gongniu Cable is committed to providing products that meet high standards of quality and safety.

Specification

  • Conductor:
    • Material: Copper (Cu)
    • Type: Class 1 (solid) or Class 2 (stranded); circular or circular compacted
  • Insulation:
    • Material: Cross-linked Polyethylene (XLPE)
  • Outer Sheath:
    • Material: Polyvinyl Chloride (PVC)
  • Key Characteristics:
    • Reliable electrical performance
    • Strong mechanical properties
    • XLPE insulation for increased power capacity and reduced dielectric loss
    • High insulation resistance for safety and efficiency
    • PVC outer sheath for good oil and abrasion resistance
  • Applicable Standards:
    • IEC 60228: Conductors of insulated cables
    • IEC 60502-1: Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um=1.2 kV) up to 30 kV (Um=36 kV) – Part 1: Cables for rated voltages of 1 kV (Um=1.2 kV) and 3 kV (Um=3.6 kV)

                      Technical Parameter

N2XY/NA2XY(YJV/YJLV) Single Core 0.6-1kV IEC 60502-1

No. of Cores and Nominal Cross Section (No. × mm²)Nominal Insulation Thickness (mm)Nominal Sheath Thickness (mm)Approx. Overall Diameter (mm)Approx. Weight (kg/km)Max. DC Resistance
of Conductor at
20℃ (Ω/km)
CuAlCuAl
1×1.50.71.45.64412.1
1×2.50.71.46.055417.4112.1
1×40.71.46.472494.617.41
1×60.71.46.995593.084.61
1×100.71.48.2140771.833.08
1×160.71.49.01991011.151.91
1×250.91.410.62951430.7271.20
1×350.91.411.63891770.5240.868
1×501.01.413.15122240.3870.641
1×701.11.414.87143000.2680.443
1×951.11.516.89683940.1930.320
1×1201.21.518.412044760.1530.253
1×1501.41.620.514845870.1240.206
1×1851.61.622.518477170.09910.164
1×2401.71.725.223859180.07540.125
1×3001.81.827.8297011300.06010.100
1×4002.01.931.2380314310.04700.0778
1×5002.22.034.7480117940.03660.0605
1×6302.42.239.2619622920.02830.0469