NYY – VV (Cu/PVC/PVC)

These power cables are used for electricity supply in low voltage installation systems. They are well adapted to underground use in industrial applications with an additional mechanical protection. These cables can be fixed on cable trays, within conduits or fixed to walls.

Application

The NYY – VV Power Cable is specifically used for electricity supply in low voltage installation systems. It is well-suited for a variety of general industrial and commercial applications. These cables can be securely installed on cable trays, routed within conduits, or directly affixed to walls. They provide a reliable power connection in environments where additional mechanical protection is not inherently required from the cable itself, relying instead on the installation method for safeguarding.

Description

Gongniu Cable’s NYY – VV power cable is engineered for robust performance and includes:

  • Conductor: The cable features high-quality copper conductors. These can be solid or stranded, in circular or compacted circular forms (Class 1 or Class 2), ensuring excellent electrical conductivity.
  • Insulation: Each conductor is insulated with Polyvinyl Chloride (PVC). This material provides strong electrical insulation and stability.
  • Outer Sheath: The entire cable is encased in a durable Polyvinyl Chloride (PVC) outer sheath. This provides comprehensive protection against common environmental factors. It offers good resistance to abrasion, moisture, and direct sunlight. The PVC also ensures adequate resistance to oil, contributing to the cable’s longevity in various settings

This construction ensures Gongniu Cable’s NYY – VV cable delivers dependable electrical and mechanical performance, high reliability, and requires minimal maintenance. Its lightweight design and good bending properties make it easy to install and handle.

Specification

The NYY – VV Power Cable is manufactured to meet stringent international quality and safety standards:

  • Conductor Requirements: It complies with IEC 60228 for conductors of insulated cables
  • Power Cable Standards: It meets the requirements of IEC 60502-1. This standard covers power cables with extruded insulation and their accessories for rated voltages from 1kV (Um=1.2kV) up to 30kV (Um=36kV). Specifically, Part 1 details specifications for cables operating at rated voltages of 1kV (Um=1.2kV) and 3kV (Um=3.6kV)

                       Technical Parameter

No. of Cores and Nominal Cross SectionMin. Number of WiresNominal Insulation ThicknessNominal
Sheath Thickness
Approx.
Overall Diameter
Approx. WeightMax. D.C .Resistance of Conductor
at 20℃
No. × mm²No.mmmmmmkg/kmΩ/km
1×1.510.81.45.84912.1
1×2.510.81.46.2617.41
1×411.01.47.0854.61
1×611.01.47.51083.08
1×1061.01.48.81571.83
1×1661.01.49.62181.15
1×2561.21.411.23200.727
1×3561.21.412.24160.524
1×5061.41.413.95510.387
1×70121.41.515.67610.268
1×95151.61.517.810300.193
1×120181.61.619.412740.153
1×150181.81.621.115540.124
1×185302.01.723.419430.0991
1×240342.21.826.325080.0754
1×300342.41.929.131230.0601
1×400532.62.032.439810.0470
1×500532.82.136.150140.0366
1×630532.82.240.063920.0283