RHZ1(YJLV) 8.7/15kV(Al/XLPE/CTS/LSZH)

Medium voltage cables for distribution networks, they are suitable for laying indoor, tunnel, cables trench and underground, it is able to bear external mechanical forces, but unable to bear heavy pulling force, it widely used in transformer stations, electric power plants and industrial plants.

Application

The RHZ1 medium voltage power cable serves multiple critical functions in electrical infrastructure. This cable works efficiently in power distribution networks across various environments. You can install it for connecting generation units to main power systems. The cable also handles plant and process connections in industrial facilities.

Installation flexibility makes this cable suitable for different environments. You can lay it directly underground for permanent installations. The cable performs well in outdoor applications where weather resistance matters. Indoor installations benefit from its compact design and safety features. Cable duct installations provide additional protection and organization.

Description

Gongniu Cable manufactures the RHZ1 using advanced materials and proven construction methods. The cable features an aluminum conductor that provides excellent electrical conductivity. Class 2 circular compacted conductors ensure reliable power transmission with minimal losses.

The insulation system uses Cross-Linked Polyethylene (XLPE) technology. This material offers superior electrical properties and long-term durability. Non-metallic semi-conducting compounds create effective conductor and insulation screens. These screens ensure uniform electric field distribution and enhanced safety.

Copper tape screening provides electromagnetic protection and fault current handling. The metallic screen can also use copper wire depending on specific requirements. Gongniu Cable selects the appropriate screening method based on application needs.

The outer sheath uses Polyvinyl (PO) compounds in various formulations. Available options include DMZ1, DMZ2, LSOH, and LSZH materials. Standard colors are black or red to meet different installation requirements.

Key Characteristics

This cable delivers excellent electrical and mechanical performance. The low dielectric loss factor ensures efficient power transmission with minimal energy waste. High insulation resistance maintains system reliability over extended periods.

The PO outer sheath provides strong resistance to UV radiation, oil exposure, and physical abrasion. These properties extend cable life in challenging environments. ZD Cable designs different cable structures and materials to meet specific application requirements.

Technical Specifications

Standards Compliance

  • IEC 60502-2: Power Cables with Extruded Insulation and Their Accessories for Rated Voltages from 1 kV (Um=1.2kV) up to 30kV (Um=36kV)
  • UNE HD 620 S3: Distribution Cables with Extruded Insulation for Rated Voltages from 3.6/6(7.2)kV

Voltage Ratings

The cable supports multiple voltage classifications:

  • 6/10kV systems with appropriate insulation thickness
  • 8.7/15kV applications for medium-scale distributions
  • 12/20kV networks for larger power requirements
  • 18/30kV installations for high-voltage distributions

Construction Details

  • Conductor: Aluminum, Class 2, circular compacted design
  • Conductor Screen: Non-metallic semi-conducting compound
  • Insulation: Cross-Linked Polyethylene (XLPE)
  • Insulation Screen: Non-metallic semi-conducting compound
  • Metallic Screen: Copper tape or copper wire options
  • Outer Sheath: Polyvinyl (PO) with various compound options

Performance Features

  • Low dielectric loss factor for energy efficiency
  • High insulation resistance for system reliability
  • UV, oil, and abrasion resistance from PO sheath
  • Flame retardant properties meeting EN 60332-1-2 standards

 

 

 

RHZ1 Medium Voltage Cable UNE HD 620 S3 CU(AL)/XLPE/PO 8.7/15kV Nominal Insulation Thickness

No. of Cores and Nominal Cross Section (mm²) Min. Number of wires Nominal Insulation Thickness (mm) Approx. Overall Diameter (mm) Approx. Weight (kg/km) Max. DC Resistance of Conductor at 20℃ (Ω/km)
No. Al Al
1X50/16 6 4.5 27.4 848 0.641
1X95/16 15 4.5 30.9 1082 0.320
1X150/25 18 4.5 34.0 1413 0.206
1X240/25 34 4.5 38.6 1848 0.125
1X400/35 53 4.5 43.5 2501 0.0778
Scroll to Top