Service Drop Cable (ANSI/ICEA S-76-474)

The conductor consists of a phase conductor and a neutral conductor. The material of the phase conductors is Aluminum or copper and may be solid, stranded circular compacted or compressed or uncompressed conductor.

Application
Primarily used for overhead service applications such as street lighting, outdoor lighting, and temporary service for construction. To be used at voltages of 600 volts phase – to – phase or less and at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for cross-linked polyethylene (XLPE) insulated conductors.

Description
The conductor consists of a phase conductor and a neutral conductor. The material of the phase conductors is  Aluminum or copper and may be solid, stranded circular compacted or compressed or uncompressed conductor. The neutral conductors are stranded round circular uncompressed aluminum or copper or aluminum-alloy conductor or ACSR or ACSR/AW etc. And the insulating material is black weather or UV-resistant thermoplastic polyethylene (PE) or cross-linked polyethylene (XLPE).
Note: Neutral conductors can be insulated or non-insulated.

Specifications
● ANSI/ICEA S-76-474 Neutral-Supported Power Cable Assemblies With Weather-Resistant Extruded Insulation Rated 600 Volts.
● ASTM B 231 Class AA, A, or B Stranded Aluminum 1350 (Excluding Unilay Compressed)
● ASTM B 400 Compact-Round Stranded Aluminum 1350 Conductors.
● ASTM B 399 Class AA, or A Stranded Aluminum-Alloy 6201 T-81 Conductors.
● ASTM B 232 Concentric-Lay-Stranded Aluminum Conductors, Coated-Steel Reinforced (ACSR)
● ASTM B 549 For Concentric-Lay-Stranded Aluminum Conductors, Aluminum-Clad Steel Reinforced (ACSR/AW)

                     Technical Parameter

Duplex Service Drop – Aluminum Conductors  
Code WordPhase ConductorBare Neutral MessengerApprox.  Diameter of CableApprox. Weight
SizeNo. of wiresNominal Insulation ThicknessSizeNo. of WiresDiameter of Wires
AWG or KcmilNo.mmAWG or KcmilNo.mmmmkg/km
AAC/XLPE+AAC
Pekingese611.14671.5611.192
Collie671.14671.5611.594
Cocker671.52671.5612.2100
Dachshund411.14471.9613.4140
Spaniel471.14471.9613.9143
Cairn471.52471.9614.6150
Doberman271.14272.4716.9220
Airedale1191.52172.7819.6280
Basset1/071.521/073.1221.8355
Malemute1/0191.521/073.1221.6350
AAC/XLPE+AAAC
Chihuahua611.1430.5871.6811.498
Vizsla671.1430.5871.6811.8100
Harrier411.1448.6972.1213.8149
Whippet471.1448.6972.1214.4154
Schnauzer271.1477.4772.6717.5235
Afghan1/071.52123.373.3722.5378
Heeler1/0191.52123.373.3722.3375
AAC/XLPE+ACSR
Setter611.1466 / 11.6811.4109
Shepherd671.1466 / 11.6811.8112
Retriever671.5266 / 11.6812.6119
Eskimo411.1446 / 12.1213.8166
Terrier471.1446 / 12.1214.4170
Yorkshire471.5246 / 12.1215.1180
Chow271.1426 / 12.6717.5262
Labrador1191.5216 / 13.0020.2339
Bloodhound1/071.521/06 / 13.3722.5425
Bull1/0191.521/06 / 13.3722.3422
 
Triplex Service Drop – Aluminum Conductors 
Code WordPhase ConductorBare Neutral MessengerApprox.  Diameter of CableApprox. Weight
SizeNo. of WiresNominal Insulation ThicknessSizeNo. of WiresDiameter of Wires
AWG or KcmilNo.mmAWG or KcmilNo.mmmmkg/km
AAC/XLPE+AAC
Haiotis611.14671.5612.6148
Pike670.76671.5612.1139
Patella671.14671.5613.2154
Albus671.52671.5614.3170
Fusus411.14471.9615.0221
Limpet471.14671.5614.9208
Oyster471.14471.9615.8230
Argo471.52471.9616.9249
Clam271.14272.4719.0347
Thia271.52272.4720.1370
Mussel271.14471.9617.9312
Pyrula171.52172.7822.4465
Hyas1191.52172.7822.2450
Snail1/071.52272.4723.2517
Murex1/071.521/073.1224.6572
Purpura1/0191.521/073.1224.4554
Nassa2/071.522/073.5027.1706
Trophon2/0191.522/073.5026.8684
Quahog3/072.033/073.9331.3920
Ione3/0192.033/073.9331.0892
Melita3/0191.523/0192.3929.7845
Coquina4/071.524/074.4233.01082
Tusk4/072.034/074.4234.51134
Apus4/0192.034/074.4234.11098
Portunus4/0192.034/0192.6834.21098
Chiton266.8192.03266.8193.0138.41379
Alverno300372.034/0192.6837.81386
Nannynose336.4192.03336.4193.3842.41707
AAC/XLPE+AAAC
Minex611.1430.5871.6812.8154
Hippa671.1430.5871.6813.4160
 
Code WordPhase ConductorBare Neutral MessengerApprox.  Diameter of CableApprox. Weight
SizeNo. of WiresNominal Insulation ThicknessSizeNo. of WiresDiameter of Wires
AWG or KcmilNo.mmAWG or KcmilNo.mmmmkg/km
AAC/XLPE+AAAC
Artemia411.1430.5871.6814.4205
Crad471.1430.5871.6815.2214
Prawn411.1448.6972.1215.3231
Barnacle471.1448.6972.1216.1239
Solaster271.1448.6972.1218.2322
Pagurus271.5248.6972.1219.3345
Shrimp271.1477.4772.6719.4362
Lobster271.5277.4772.6720.5385
Sanderab1/071.5277.4772.6723.6532
Echinus1/0191.5277.4772.6723.4514
Gammarus1/071.52123.373.3725.1597
Leda1/0191.52123.373.3724.9579
Crayfish2/071.5297.6573.0026.0655
Sipho2/0191.5297.6573.0025.7633
Abalone2/071.52123.373.3726.8691
Spirula2/0191.52123.373.3726.5669
Dungenese2/071.52155.473.7827.7736
Cyclops2/0191.52155.473.7827.4714
Slug3/071.52123.373.3728.6809
Fulgur3/0191.52123.373.3728.4781
Balanus3/0192.03123.373.3729.8828
Stonecrab3/071.52195.774.2530.5904
Flustra3/0191.52195.774.2530.3884
Crisia3/0192.03195.774.2531.7931
Squid4/071.52155.473.7831.61001
Arca4/0191.52155.473.7831.3966
Bugula4/0192.03155.473.7832.71018
Kingcrab4/071.52246.974.7733.81131
Lepas4/0191.52246.974.7733.41096
Cassis4/0192.03246.974.7734.91147
Cyphoma4/071.52123.373.3730.8957
Mitre4/0191.52123.373.3730.4921
Argonaut336.4192.03246.974.7740.51579
Nautilis336.4192.03394.5193.6643.41787
 
Code WordPhase ConductorBare Neutral MessengerApprox.  Diameter of CableApprox. Weight
SizeNo. of WiresNominal Insulation ThicknessSizeNo. of wiresDiameter of Wires
AWG or KcmilNo.mmAWG or KcmilNo.mmmmkg/km
AAC/XLPE+ACSR
Paludina611.1466 / 11.6812.8165
Voluta671.1466 / 11.6813.4171
Bolma671.5266 / 11.6814.5188
Scallop411.1466 / 11.6814.4217
Strombus471.1466 / 11.6815.1225
Carnea471.5266 / 11.6816.2244
Whelk411.1446 / 12.1215.3249
Periwinkle471.1446 / 12.1216.1257
Calma471.5246 / 12.1217.2277
Cockle271.1446 / 12.1218.2340
Gebia271.5246 / 12.1219.3363
Conch271.1426 / 12.6719.4391
Uca271.5226 / 12.6720.5414
Vermeths171.5216 / 13.0022.9520
Atya1191.5216 / 13.0022.6506
Janthina1/071.5226 / 12.6723.6561
Ranella1/0191.5226 / 12.6723.4543
Neritina1/071.521/06 / 13.3725.1642
Cenia1/0191.521/06 / 13.3724.9624
Cavolinia2/071.5216 / 13.0026.0691
Clio2/0191.5216 / 13.0025.7669
Runcina2/071.522/06 / 13.7827.7794
Triton2/0191.522/06 / 13.7827.4772
Sanddollar3/071.521/06 / 13.3728.6854
Aega3/0191.521/06 / 13.3728.4827
Pisa3/0192.031/06 / 13.3729.8874
Cherrystone3/071.523/06 / 14.2530.5983
Mursia3/0191.523/06 / 14.2530.3956
Mysis3/0192.033/06 / 14.2531.71003
Cuttlefish4/071.522/06 / 13.7831.71059
 
Code WordPhase ConductorBare Neutral MessengerApprox.  Diameter of CableApprox. Weight
SizeNo. of WiresNominal Insulation ThicknessSizeNo. of wiresDiameter of Wires
AWG or KcmilNo.mmAWG or KcmilNo.mmmmkg/km
AAC/XLPE+ACSR
Cerapus4/0191.522/06 / 13.7831.31024
Nepatus4/0192.032/06 / 13.7832.71075
Razor4/071.524/06 / 14.7733.81222
Zuzara4/0191.524/06 / 14.7733.41187
Alima4/0192.034/06 / 14.7734.91238
Callista266.8192.033/06 / 14.2536.71350
Dosinia266.8192.03266.818 / 13.0938.71438
Cowry336.4192.034/06 / 14.7740.51670
Limpet336.4192.03336.418 / 13.4742.71782
 
Quadruplex Service Drop – Aluminum Conductors
Code WordPhase ConductorBare Neutral MessengerApprox.  Diameter of CableApprox. Weight
SizeNo. of WiresNominal Insulation ThicknessSizeNo. of wiresDiameter of Wires
AWG or KcmilNo.mmAWG or KcmilNo.mmmmkg/km
AAC/XLPE+AAC
Quarter611.14671.5614.4203
Clydesdate411.14471.9617.1302
Pinto471.14471.9618.1315
Mustang271.14272.4721.7474
Shire1191.52172.7825.4616
Libyan1/071.521/073.1228.2784
Criollo1/0191.521/073.1227.9757
Orloff2/071.522/073.5030.9965
Percheron2/0191.522/073.5030.6931
Mongolian3/071.523/073.9334.11190
Hanoverian3/0191.523/0192.3933.81148
Singlefoot4/071.524/074.4237.61474
Oldenburg4/0191.524/0192.6837.21421
Lippizaner336.4192.03336.4193.3848.32322
AAC/XLPE+AAAC
Bay611.1430.5871.6814.7209
French-Coach671.1430.5871.6815.4218
German-Coach411.1448.6972.1217.4312
Arabian471.1448.6972.1218.4324
Belgian271.1477.4772.6722.0489
Viatka1/071.5277.4772.6727.4743
Thoroughbred2/0191.52155.473.7831.1962
Celtic2/071.52123.373.3730.7950
Norman2/0191.52123.373.3730.3917
Donkey3/071.52123.373.3733.01126
Burro3/0191.52123.373.3732.71085
Dobbin3/071.52195.774.2534.61229
Trotter3/0191.52195.774.2534.31188
Roan4/071.52123.373.3735.71348
Gotland4/0191.52123.373.3735.21295
Bali4/071.52155.473.7836.51393
Skyros4/0191.52155.473.7836.01340
Pony4/071.52246.974.7738.31522
 
Code WordPhase ConductorBare Neutral MessengerApprox.  Diameter of CableApprox. Weight
SizeNo. of WiresNominal Insulation ThicknessSizeNo. of WiresDiameter of Wires
AWG or KcmilNo.mmAWG or KcmilNo.mmmmkg/km
AAC/XLPE+AAAC
Walking4/0191.52246.974.7737.81470
Exmoor336.4192.03246.9192.8946.82193
Breton336.4192.03394.5193.6649.12402
AAC/XLPE+ACSR
Morochuca611.1466 / 11.6814.7221
Chola671.1466 / 11.6815.4229
Morgan411.1446 / 12.1217.4330
Hackney471.1446 / 12.1218.4342
Palomino271.1426 / 12.6722.0518
Albino1191.5216 / 13.0025.8672
Standardbred1/071.521/06 / 13.3728.6854
Costena1/0191.521/06 / 13.3728.3827
Chicoteagues2/071.522/06 / 13.7831.51053
Grullo2/0191.522/06 / 13.7831.11022
Mare3/071.523/06 / 14.2534.61301
Suffolk3/0191.523/06 / 14.2534.31260
Stallion4/071.524/06 / 14.7738.31614
Appaloosa4/0191.524/06 / 14.7737.81561
Gelding336.4192.034/06 / 14.7746.72285
Bronco336.4192.03336.418 / 13.4748.62396