Stranded Hard Drawn Copper Conductors for Overhead Lines

Bare Stranded Hard-Drawn Copper Conductors

Shape of conductor: Hard-drawn copper stranded wire

Sectional area: 0.5-1000mm2

Insulation: N/A

Standard: BS 7884 DIN 48201 / 1

Application
Bare stranded hard-drawn copper conductor is suitable for overhead transmission and distribution networks applications, where the highest electrical conductivity per unit area and good strength-to-weight ratio are required.
 
 
Standard
Bare stranded hard-drawn copper conductor can be supplied to meet various International Standards as follows:

BS 7884
DIN 48201 / 1
However, Hongda Cables can also supply a range of alternative designs to meet customer-specified requirements.
 
CONSTRUCTION :

 
Conductor : Hard-drawn copper stranded wire
 
 
PARAMETER :
Dimensions and WeightsElectrical Information
 NominalNumber OfOverallNet weightConductor DC (maks.)Calculated Min.
Cross sectionWire/wire Diadiameter approxapprox.resistance at 20 °C (maks.)Break Strength
mm² Wire diametermmkg/kmohm/kmkN.
10 rm7/1.323,9685,81,9153,96
16 rm7/1.705,10142,41,1546,50
25 rm7/2.126,36221,40,7429,99
35 rm7/2.507,50308,00,53413,91
50 rm7/3.009,00443,50,36919,57
50 rm19/1.809,00436,30,38419,36
70 rm19/2.1210,60605,20,27526,55
95 rm19/2.5012,50841,70,19836,93
120 rm19/2.8014,001056,00,15845,27
150 rm37/2.2415,681320,00,12757,73
185 rm37/2.5017,501644,00,10271,91
240 rm61/2.2420,202179,00,07795,17
300 rm61/2.5022,552715,00,062118,56